Rainwater Harvesting & Roof Drainage
Annual harvestable rainwater, tank size and share of demand met, plus design peak runoff and the number of downpipes.
How it works — Rainwater Harvesting & Roof Drainage
Inputs
- A
- Roof catchment area (m²)
- R
- Annual rainfall (mm)
- C
- Runoff coefficient
- i
- Design rainfall intensity (mm/h)
Formula
- V = A·R·C·η
- Q = C·i·A
Results
- V
- Annual harvestable water
- Q
- Design peak runoff
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
V = A·R·C·η · Q = C·i·A · n = ⌈Q / Q_leader⌉
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Assumptions
- Tank sized by the simplified approach (5 % of the lesser of annual yield and demand).
- Downpipe capacities from IPC Table 1106.2 for vertical leaders.
References
- BS EN 16941-1: On-site non-potable water systems — rainwater
- International Plumbing Code, Table 1106.2
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Architectural tools
- Architectural Shadow Cast & Sun Path Simulator Interactive 3D sun-path and shadow study: see where a building's shadow falls at any time of day on the solstices and equinoxes. Open tool
- Architectural Stair Calculator Riser count and height, tread run, stair angle and the 2R + T comfort rule from the total floor-to-floor rise. Open tool
- Architectural Roof Pitch Calculator Roof angle, pitch in 12, percent slope and rafter length from rise and run. Open tool
- Architectural Wall Area & Paint Calculator Paintable wall area and litres of paint for a rectangular room, net of doors and windows. Open tool