Level 1 — Basic calculation

Sensor Signal Scaling: 4–20 mA, RTD & Strain Gauge

Convert 4–20 mA loop current to process value (with NAMUR fault bands), Pt100/Pt1000 resistance to temperature, and strain to bridge output voltage.

How it works — Sensor Signal Scaling: 4–20 mA, RTD & Strain Gauge

4–20 mA x LRV … URV

Inputs

4–20 mA
Loop current (blank to convert a value) (mA)
LRV … URV
Upper range value (at 20 mA)

Formula

  • x = LRV + (I − 4)/16·(URV − LRV)
  • R = R₀(1 + AT + BT²)
  • V_o/V_ex = n·GF·ε/4

Results

x
Process value
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

x = LRV + (I − 4)/16·(URV − LRV) · R = R₀(1 + AT + BT²) · V_o/V_ex = n·GF·ε/4

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 1 — Basic calculation

A direct engineering equation.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Linear transmitter; IEC 60751 coefficients for platinum RTDs; ideal bridge with equal arm resistances.

References

  • IEC 60751: Industrial platinum resistance thermometers
  • NAMUR NE 43: Standardization of the signal level for failure information
  • ISA-50.00.01: Compatibility of analog signals

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.