Level 1 — Basic calculation
Three-Phase Power
Real, apparent and reactive power of a balanced three-phase load.
How it works — Three-Phase Power
Inputs
- VLL
- Line-to-line voltage (V)
- IL
- Line current (A)
- cos φ
- Power factor
Formula
- S = √3·V·I
- P = S·cosφ
- Q = √(S² − P²)
Results
- P
- Real power
- S
- Apparent power
- Q
- Reactive power
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
S = √3·V·I · P = S·cosφ · Q = √(S² − P²)
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 1 — Basic calculation
A direct engineering equation.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Sinusoidal supply; three-phase loads are balanced.
- Power factor is the displacement power factor (no harmonics).
References
- IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Ohm's Law & Power Current, power and conductance from voltage and resistance. Open tool
- Electrical Engineering AC Power & Power Factor Correction Real, reactive and apparent power with the power triangle, plus the capacitor bank that raises the power factor to a target. Open tool
- Electrical Engineering Series & Parallel Resistors Equivalent resistance of resistors connected in series or in parallel. Open tool
- Electrical Engineering DC Circuit Solver (Kirchhoff's Laws, Nodal Analysis) Solve any linear DC network of resistors and voltage and current sources: node voltages, branch currents, powers and the KCL/KVL check, by modified nodal analysis. Open tool