Natural & Cross Ventilation

Airflow and air changes per hour from wind-driven cross ventilation and the stack effect through two openings.

How it works — Natural & Cross Ventilation

U V H

Inputs

V
Room volume (m³)
U
Wind speed at building height (m/s)
H
Height between openings (m)

Formula

  • Q_w = C_d·A·U·√ΔC_p
  • Q_s = C_d·A·√(2gHΔT/T)

Results

ACH
Air changes per hour
Q
Ventilation rate

Windward–leeward, typically 0.4–1.0

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

Q_w = C_d·A·U·√ΔC_p · Q_s = C_d·A·√(2gHΔT/T) · ACH = 3600Q/V

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Assumptions

  • Openings in series; wind and stack flows combined as the root of the sum of squares.
  • Steady wind; internal partitions and insect screens not considered.

References

  • CIBSE AM10: Natural ventilation in non-domestic buildings
  • BS 5925: Ventilation principles

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.