Natural & Cross Ventilation
Airflow and air changes per hour from wind-driven cross ventilation and the stack effect through two openings.
How it works — Natural & Cross Ventilation
Inputs
- V
- Room volume (yd³)
- U
- Wind speed at building height (ft/s)
- H
- Height between openings (ft)
Formula
- Q_w = C_d·A·U·√ΔC_p
- Q_s = C_d·A·√(2gHΔT/T)
Results
- ACH
- Air changes per hour
- Q
- Ventilation rate
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
Q_w = C_d·A·U·√ΔC_p · Q_s = C_d·A·√(2gHΔT/T) · ACH = 3600Q/V
Formulas are evaluated in SI units; inputs and results are converted.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Assumptions
- Openings in series; wind and stack flows combined as the root of the sum of squares.
- Steady wind; internal partitions and insect screens not considered.
References
- CIBSE AM10: Natural ventilation in non-domestic buildings
- BS 5925: Ventilation principles
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Architectural tools
- Architectural Shadow Cast & Sun Path Simulator Interactive 3D sun-path and shadow study: see where a building's shadow falls at any time of day on the solstices and equinoxes. Open tool
- Architectural Stair Calculator Riser count and height, tread run, stair angle and the 2R + T comfort rule from the total floor-to-floor rise. Open tool
- Architectural Roof Pitch Calculator Roof angle, pitch in 12, percent slope and rafter length from rise and run. Open tool
- Architectural Wall Area & Paint Calculator Paintable wall area and litres of paint for a rectangular room, net of doors and windows. Open tool