Level 3 — Standard / code based

Isolated Square Footing (Bearing, Punching, Flexure)

Footing size from the net allowable bearing pressure, punching and one-way shear checks and the reinforcement each way of an isolated square footing under a column.

How it works — Isolated Square Footing (Bearing, Punching, Flexure)

P qu B

Inputs

P
Service dead load P_D (kN)
qa
Allowable gross bearing pressure (kPa)

Formula

  • A = (P_D + P_L)/q_net
  • V_u ≤ 0.75·0.33√f′c·b₀d
  • V_u ≤ 0.75·0.17√f′c·Bd
  • M_u = q_u·B·ℓ²/2

Results

B
Footing size (square)
qu
Factored soil pressure q_u
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

A = (P_D + P_L)/q_net · V_u ≤ 0.75·0.33√f′c·b₀d · V_u ≤ 0.75·0.17√f′c·Bd · M_u = q_u·B·ℓ²/2

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 3 — Standard / code based

Follows the method of the named design standard within the stated scope; it does not check every provision of that standard.

Design standard / method: ACI 318-19 (SI) — rectangular sections, flexure and one-way shear only; other provisions not checked

Assumptions

  • Concentric axial load, square column at the centre, uniform soil pressure.
  • Square column: the governing ACI two-way shear expression is 0.33√f′c.
  • Site-specific geotechnical investigation required for the allowable bearing pressure.

References

  • ACI 318-19: Building Code Requirements for Structural Concrete (SI)
  • B. M. Das, Principles of Foundation Engineering

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.