Level 2 — Engineering approximation
Building Electrical Load & Transformer Size
Connected and demand load, power factor, current, diversity and the next standard transformer size from a load schedule with your own demand factors.
How it works — Building Electrical Load & Transformer Size
Inputs
- P·DF
- Load schedule
Formula
- P_d = Σ P_i·DF_i
- S_d = √(P_d² + Q_d²)
- I = S/(√3·V)
- S_design = S_d(1 + growth)
Results
- Σ P·DF
- Demand load
- S, I
- Demand current
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
P_d = Σ P_i·DF_i · S_d = √(P_d² + Q_d²) · I = S/(√3·V) · S_design = S_d(1 + growth)
Formulas are evaluated in SI units; inputs and results are converted.
The default schedule is the industrial-facility example: two motors, lighting, HVAC and EV charging. Change the EV line and every result updates.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Demand factors and power factors are the values you enter; no code demand factors are built in.
- Loads are balanced across the phases.
References
- IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
- IEEE Std 241 (Gray Book): Commercial building power systems
- IEC 60364-3: Assessment of general characteristics
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Panel Schedule & Phase Balance Phase loads, imbalance, phase currents and demand of a three-phase panelboard from a list of circuits, with a phase-balance chart. Open tool
- Electrical Engineering Standby Generator Sizing (Running Load & Motor Starting) Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance. Open tool
- Electrical Engineering Cable Sizing (Ampacity, Voltage Drop, Fault) Smallest copper conductor for a circuit after temperature and grouping derating, breaker coordination, voltage drop and short-circuit withstand. Open tool
- Electrical Engineering Cable Voltage Drop Resistive voltage drop and power loss in single-phase and three-phase cable runs. Open tool
- Electrical Engineering Transformer Currents, Fault Level & Regulation Primary and secondary full-load currents, turns ratio, secondary short-circuit current and voltage regulation of a transformer. Open tool