Level 1 — Basic calculation
Harmonics, THD & Waveform
Total harmonic distortion, true RMS, crest factor and K-factor from a harmonic spectrum, with the distorted waveform, the spectrum and IEEE 519 voltage limits.
How it works — Harmonics, THD & Waveform
Inputs
- V1
- Fundamental (RMS, V or A)
- f
- Fundamental frequency (Hz)
- Vh
- Harmonics (order:% of fundamental[:phase °])
Formula
- THD = √(Σ_{h≥2} V_h²)/V₁
- V_rms = V₁√(1 + THD²)
- K = Σ(I_h/I)²h²/Σ(I_h/I)²
Results
- THD
- Total harmonic distortion THD (of fundamental)
- Vrms
- True RMS
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
THD = √(Σ_{h≥2} V_h²)/V₁ · V_rms = V₁√(1 + THD²) · K = Σ(I_h/I)²h²/Σ(I_h/I)²
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 1 — Basic calculation
A direct engineering equation.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Steady-state periodic waveform described by its Fourier components.
- The IEEE 519 limits shown are the voltage limits at the point of common coupling.
References
- IEEE Std 519-2022: Harmonic control in electric power systems
- IEEE Std 1459: Definitions for power quantities under non-sinusoidal conditions
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering AC Power & Power Factor Correction Real, reactive and apparent power with the power triangle, plus the capacitor bank that raises the power factor to a target. Open tool
- Electrical Engineering Transformer Currents, Fault Level & Regulation Primary and secondary full-load currents, turns ratio, secondary short-circuit current and voltage regulation of a transformer. Open tool
- Electrical Engineering ADC / DAC Resolution, Sampling & Aliasing LSB size, output code, ideal SQNR, Nyquist frequency, aliasing and data rate of an analog-to-digital converter, with a sampling chart. Open tool
- Electrical Engineering Per-Unit System & Change of Base Base impedance and current of a three-phase system, conversion of ohms to per unit and of a per-unit impedance to a new MVA and kV base. Open tool