Level 1 — Basic calculation

Harmonics, THD & Waveform

Total harmonic distortion, true RMS, crest factor and K-factor from a harmonic spectrum, with the distorted waveform, the spectrum and IEEE 519 voltage limits.

How it works — Harmonics, THD & Waveform

1 3 5 7 THD

Inputs

V1
Fundamental (RMS, V or A)
f
Fundamental frequency (Hz)
Vh
Harmonics (order:% of fundamental[:phase °])

Formula

  • THD = √(Σ_{h≥2} V_h²)/V₁
  • V_rms = V₁√(1 + THD²)
  • K = Σ(I_h/I)²h²/Σ(I_h/I)²

Results

THD
Total harmonic distortion THD (of fundamental)
Vrms
True RMS
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

THD = √(Σ_{h≥2} V_h²)/V₁ · V_rms = V₁√(1 + THD²) · K = Σ(I_h/I)²h²/Σ(I_h/I)²

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 1 — Basic calculation

A direct engineering equation.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Steady-state periodic waveform described by its Fourier components.
  • The IEEE 519 limits shown are the voltage limits at the point of common coupling.

References

  • IEEE Std 519-2022: Harmonic control in electric power systems
  • IEEE Std 1459: Definitions for power quantities under non-sinusoidal conditions

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.