Overcurrent Relay Time–Current Curves & Coordination

Operating times of two inverse-time overcurrent relays (IEC or IEEE curves) at a fault current, the coordination time interval and the log–log time–current curves.

How it works — Overcurrent Relay Time–Current Curves & Coordination

If I t Δt

Inputs

If
Fault current (A)
Is
Pickup current I_s (A)
TMS
Time multiplier / dial

Formula

  • IEC: t = TMS·k/((I/I_s)^α − 1)
  • IEEE: t = TD·(A/(M^p − 1) + B)
  • Δt = t_up − t_down ≥ CTI

Results

t
Downstream relay operating time
Δt
Coordination time interval
Downstream relay
Upstream relay
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

IEC: t = TMS·k/((I/I_s)^α − 1) · IEEE: t = TD·(A/(M^p − 1) + B) · Δt = t_up − t_down ≥ CTI

Formulas are evaluated in SI units; inputs and results are converted.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 3 — Standard / code based

Follows the method of the named design standard within the stated scope; it does not check every provision of that standard.

Design standard / method: IEC 60255-151 / IEEE C37.112 inverse-time curve equations; coordination checked at one fault current

Assumptions

  • Inverse-time elements only (no instantaneous or definite-time stages); CT saturation ignored.
  • Both relays see the same fault current.

References

  • IEC 60255-151: Functional requirements for over/under current protection
  • IEEE Std C37.112: Inverse-time characteristic equations for overcurrent relays
  • IEEE Std 242 (Buff Book): Protection and coordination

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.