Level 2 — Engineering approximation
Short-Circuit Current (Transformer-Fed Fault)
Prospective three-phase and line-to-line fault currents and the peak current at a transformer's secondary bus and at the end of a cable, from the utility fault level, transformer impedance and cable data.
How it works — Short-Circuit Current (Transformer-Fed Fault)
Inputs
- SkQ
- Utility fault level S″kQ (MVA)
- U
- System voltage (line-to-line, fault side) (V)
- ZT
- Transformer impedance u_k (%)
- ZL
- Cable length (ft)
Formula
- Z_Q = c·U²/S″_kQ
- Z_T = u_k·U²/S_rT
- I″k = c·U/(√3·|Z_k|)
- i_p = κ√2·I″k, κ = 1.02 + 0.98e^(−3R/X)
Results
- Ik
- Fault current at the bus I″k (3-phase)
- ip
- Peak current at the bus i_p
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
Z_Q = c·U²/S″_kQ · Z_T = u_k·U²/S_rT · I″k = c·U/(√3·|Z_k|) · i_p = κ√2·I″k, κ = 1.02 + 0.98e^(−3R/X)
Formulas are evaluated in SI units; inputs and results are converted.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Design standard / method: IEC 60909-0 equivalent voltage source method, three-phase symmetrical fault only (simplified)
Assumptions
- Three-phase bolted (zero-impedance) fault; impedances are added as complex values referred to the fault voltage.
- Motor contribution and load currents are ignored.
- Cable resistance at 20 °C (gives the maximum fault current).
References
- IEC 60909-0: Short-circuit currents in three-phase a.c. systems
- IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
- IEEE Std 551 (Violet Book): Short-circuit currents
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Transformer Currents, Fault Level & Regulation Primary and secondary full-load currents, turns ratio, secondary short-circuit current and voltage regulation of a transformer. Open tool
- Electrical Engineering Cable Sizing (Ampacity, Voltage Drop, Fault) Smallest copper conductor for a circuit after temperature and grouping derating, breaker coordination, voltage drop and short-circuit withstand. Open tool
- Electrical Engineering Overcurrent Relay Time–Current Curves & Coordination Operating times of two inverse-time overcurrent relays (IEC or IEEE curves) at a fault current, the coordination time interval and the log–log time–current curves. Open tool
- Electrical Engineering Per-Unit System & Change of Base Base impedance and current of a three-phase system, conversion of ohms to per unit and of a per-unit impedance to a new MVA and kV base. Open tool