Occupant Load & Egress

Occupant load, number of exits, exit and stair widths and travel-distance limit for a floor area and occupancy (IBC-based, preliminary).

How it works — Occupant Load & Egress

W OL

Inputs

A
Floor area (ft²)
n
Exits provided
W
Clear width of each exit door (in)

Formula

  • OL = A / load factor
  • W = OL × 0.2 in

Results

OL
Occupant load
n
Required number of exits
W
Required clear door/corridor exit width

Overrides the area-based calculation, e.g. for fixed seating

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

OL = area / load factor · W = OL × 0.2 in (0.3 in stairs)

Formulas are evaluated in SI units; inputs and results are converted.

Preliminary check only: requirements vary by jurisdiction and building classification; confirm with the governing code and authority.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Assumptions

  • IBC 2021 Table 1004.5 load factors and §1005.3 capacity factors (not the reduced factors for sprinklered buildings with voice alarm).
  • Exits are equally sized and remotely located; common path and dead-end limits are not checked.

References

  • International Building Code 2021, §1004–1006, §1017 (preliminary)
  • NFPA 101 Life Safety Code (comparable requirements)

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.