Level 3 — Standard / code based
Cable Sizing (Ampacity, Voltage Drop, Fault)
Smallest copper conductor for a circuit after temperature and grouping derating, breaker coordination, voltage drop and short-circuit withstand.
How it works — Cable Sizing (Ampacity, Voltage Drop, Fault)
Inputs
- I
- Design current I_b (A)
- L
- One-way length (ft)
- V
- Supply voltage (V)
- Ta
- Ambient temperature (°F)
Formula
- I_b ≤ I_n ≤ I_z
- ΔV = k·I·ρL/S
- S ≥ I_k√t/k
Results
- S
- Selected conductor
- Iz
- Derated ampacity I_z
- ΔV
- Voltage drop
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
I_b ≤ I_n ≤ I_z = I_table·k_T·k_G · ΔV% = k·I·ρL/(S·V) · S ≥ I_k√t/k
Formulas are evaluated in SI units; inputs and results are converted.
Metric uses IEC 60364-5-52 tables (installation method C); imperial uses NEC Table 310.16 with the 240.4(D) small-conductor limits. Check the installation method and terminal ratings for your site.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 3 — Standard / code based
Follows the method of the named design standard within the stated scope; it does not check every provision of that standard.
Design standard / method: IEC 60364-5-52 (method C) or NEC Table 310.16 ampacities, IEC 60364-5-54 adiabatic check
Assumptions
- Copper conductors; resistance at the insulation's maximum temperature (conservative).
- Ambient correction √[(T_max − T_a)/(T_max − 30)] relative to 30 °C tables.
- Reactance is ignored in the voltage drop (small cables); harmonics are not considered.
- Short-circuit check uses the adiabatic equation with k = 115 (PVC) or 143 (XLPE).
References
- IEC 60364-5-52: Selection and erection — wiring systems (Tables B.52.4, B.52.5)
- IEC 60364-5-54 / IEC 60364-4-43: protection against overcurrent
- NFPA 70 National Electrical Code, Table 310.16 and 240.4(D)
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Cable Voltage Drop Resistive voltage drop and power loss in single-phase and three-phase cable runs. Open tool
- Electrical Engineering Building Electrical Load & Transformer Size Connected and demand load, power factor, current, diversity and the next standard transformer size from a load schedule with your own demand factors. Open tool
- Electrical Engineering Panel Schedule & Phase Balance Phase loads, imbalance, phase currents and demand of a three-phase panelboard from a list of circuits, with a phase-balance chart. Open tool
- Electrical Engineering Standby Generator Sizing (Running Load & Motor Starting) Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance. Open tool