Level 2 — Engineering approximation
Grounding: Rod & Grid Resistance, Touch & Step Voltage
Ground rod and grid resistance, ground potential rise and the tolerable touch and step voltages for a substation grid (preliminary IEEE 80 screening).
How it works — Grounding: Rod & Grid Resistance, Touch & Step Voltage
Inputs
- ρ
- Soil resistivity ρ (Ω·m)
- L
- Rod length (m)
- A
- Grid area (m²)
- LT
- Total buried conductor length L_T (m)
- IG
- Maximum grid current I_G (A)
Formula
- R_rod = ρ/(2πL)(ln(4L/a) − 1)
- R_g = ρ[1/L_T + 1/√(20A)(1 + 1/(1 + h√(20/A)))]
- E_touch = (1000 + 1.5C_sρ_s)k/√t_s
Results
- Rg
- Grid resistance R_g
- Etouch
- Tolerable touch voltage
- Estep
- Tolerable step voltage
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
R_rod = ρ/(2πL)(ln(4L/a) − 1) · R_g = ρ[1/L_T + 1/√(20A)(1 + 1/(1 + h√(20/A)))] · E_touch = (1000 + 1.5C_sρ_s)k/√t_s
The defaults follow the square-grid example of IEEE Std 80-2013 Annex B.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Design standard / method: IEEE Std 80-2013 equations: Sverak grid resistance, tolerable touch and step voltages
Assumptions
- Uniform soil resistivity; the grid is treated as an equivalent area with a total conductor length.
- Mesh and step voltages of the actual grid geometry are not computed.
- Body resistance 1000 Ω per IEEE 80.
References
- IEEE Std 80-2013: Guide for safety in AC substation grounding
- IEEE Std 142 (Green Book): Grounding of industrial and commercial power systems
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Short-Circuit Current (Transformer-Fed Fault) Prospective three-phase and line-to-line fault currents and the peak current at a transformer's secondary bus and at the end of a cable, from the utility fault level, transformer impedance and cable data. Open tool
- Electrical Engineering Overcurrent Relay Time–Current Curves & Coordination Operating times of two inverse-time overcurrent relays (IEC or IEEE curves) at a fault current, the coordination time interval and the log–log time–current curves. Open tool
- Electrical Engineering Per-Unit System & Change of Base Base impedance and current of a three-phase system, conversion of ohms to per unit and of a per-unit impedance to a new MVA and kV base. Open tool
- Electrical Engineering Load Flow (Newton–Raphson Power Flow) Bus voltages and angles, generator outputs, line flows and losses of an N-bus network solved by the Newton–Raphson method, with a one-line view. Open tool