Level 2 — Engineering approximation

Grounding: Rod & Grid Resistance, Touch & Step Voltage

Ground rod and grid resistance, ground potential rise and the tolerable touch and step voltages for a substation grid (preliminary IEEE 80 screening).

How it works — Grounding: Rod & Grid Resistance, Touch & Step Voltage

L A, LT IG ρ Etouch, Estep

Inputs

ρ
Soil resistivity ρ (Ω·m)
L
Rod length (m)
A
Grid area (m²)
LT
Total buried conductor length L_T (m)
IG
Maximum grid current I_G (A)

Formula

  • R_rod = ρ/(2πL)(ln(4L/a) − 1)
  • R_g = ρ[1/L_T + 1/√(20A)(1 + 1/(1 + h√(20/A)))]
  • E_touch = (1000 + 1.5C_sρ_s)k/√t_s

Results

Rg
Grid resistance R_g
Etouch
Tolerable touch voltage
Estep
Tolerable step voltage
Ground rod
Grid
Fault
Surface layer
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

R_rod = ρ/(2πL)(ln(4L/a) − 1) · R_g = ρ[1/L_T + 1/√(20A)(1 + 1/(1 + h√(20/A)))] · E_touch = (1000 + 1.5C_sρ_s)k/√t_s

The defaults follow the square-grid example of IEEE Std 80-2013 Annex B.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 2 — Engineering approximation

A preliminary engineering model with the simplifications listed under Assumptions.

Design standard / method: IEEE Std 80-2013 equations: Sverak grid resistance, tolerable touch and step voltages

Assumptions

  • Uniform soil resistivity; the grid is treated as an equivalent area with a total conductor length.
  • Mesh and step voltages of the actual grid geometry are not computed.
  • Body resistance 1000 Ω per IEEE 80.

References

  • IEEE Std 80-2013: Guide for safety in AC substation grounding
  • IEEE Std 142 (Green Book): Grounding of industrial and commercial power systems

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.