Level 4 — Numerical analysis
Load Flow (Newton–Raphson Power Flow)
Bus voltages and angles, generator outputs, line flows and losses of an N-bus network solved by the Newton–Raphson method, with a one-line view.
How it works — Load Flow (Newton–Raphson Power Flow)
Inputs
- P, Q, |V|
- Bus data
- R, X
- Line data
Formula
- P_i − jQ_i = V_i*·Σ Y_ik V_k
- [ΔP; ΔQ] = J·[Δδ; Δ|V|] (Newton–Raphson, polar form)
Results
- |V|∠δ
- Lowest bus voltage
- P, Q
- Slack bus generation P
- Ploss
- Total losses P
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
P_i − jQ_i = V_i*·Σ Y_ik V_k · [ΔP; ΔQ] = J·[Δδ; Δ|V|] (Newton–Raphson, polar form)
The default network reproduces Saadat's three-bus Newton–Raphson example (Power System Analysis, Example 6.11).
One-line diagram
Buses with their solved voltage (pu) and angle; line labels show the real power flow in MW and its direction.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 4 — Numerical analysis
A numerical solver: matrix analysis, iteration or time integration.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Balanced, positive-sequence steady state; π-model lines on a common MVA base.
- Generator reactive-power limits, transformer taps and shunt devices are not modelled.
- Convergence tolerance 10⁻⁸ pu on the power mismatches.
References
- H. Saadat, Power System Analysis
- W. F. Tinney, C. E. Hart (1967), Power flow solution by Newton's method, IEEE Trans. PAS
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Per-Unit System & Change of Base Base impedance and current of a three-phase system, conversion of ohms to per unit and of a per-unit impedance to a new MVA and kV base. Open tool
- Electrical Engineering Short-Circuit Current (Transformer-Fed Fault) Prospective three-phase and line-to-line fault currents and the peak current at a transformer's secondary bus and at the end of a cable, from the utility fault level, transformer impedance and cable data. Open tool
- Electrical Engineering Synchronous Generator: EMF, Load Angle & Regulation Speed from frequency and poles, rated current, internal EMF, load angle, voltage regulation, shaft power and torque of a cylindrical-rotor synchronous generator. Open tool
- Electrical Engineering Overcurrent Relay Time–Current Curves & Coordination Operating times of two inverse-time overcurrent relays (IEC or IEEE curves) at a fault current, the coordination time interval and the log–log time–current curves. Open tool