Level 2 — Engineering approximation
Synchronous Generator: EMF, Load Angle & Regulation
Speed from frequency and poles, rated current, internal EMF, load angle, voltage regulation, shaft power and torque of a cylindrical-rotor synchronous generator.
How it works — Synchronous Generator: EMF, Load Angle & Regulation
Inputs
- S
- Load (apparent power) (kVA)
- Vφ
- Line-to-line voltage (V)
- Xs
- Synchronous reactance X_s (per phase) (Ω)
- p
- Number of poles
Formula
- n_s = 120f/p
- E_A = V_φ + (R_A + jX_s)·I_A
- VR = (E_A − V_φ)/V_φ
- P_max = 3E_AV_φ/X_s
Results
- EA
- Internal EMF (line-to-line)
- δ
- Load (power) angle δ
- ns
- Synchronous speed
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
n_s = 120f/p · E_A = V_φ + (R_A + jX_s)·I_A · VR = (E_A − V_φ)/V_φ · P_max = 3E_AV_φ/X_s
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Cylindrical (round) rotor; constant synchronous reactance (no saturation).
- Wye-connected armature.
- Sinusoidal supply; three-phase loads are balanced.
References
- S. J. Chapman, Electric Machinery Fundamentals
- IEEE Std 115: Test procedures for synchronous machines
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Standby Generator Sizing (Running Load & Motor Starting) Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance. Open tool
- Electrical Engineering Per-Unit System & Change of Base Base impedance and current of a three-phase system, conversion of ohms to per unit and of a per-unit impedance to a new MVA and kV base. Open tool
- Electrical Engineering Load Flow (Newton–Raphson Power Flow) Bus voltages and angles, generator outputs, line flows and losses of an N-bus network solved by the Newton–Raphson method, with a one-line view. Open tool
- Electrical Engineering Motor Sizing & Full-Load Current Standard motor rating for a load, with synchronous and rated speed, torque, full-load and starting current. Open tool