Level 2 — Engineering approximation
Off-Grid Solar & Battery System Sizing
Battery bank, PV array, inverter and charge controller for an off-grid system from the daily energy, days of autonomy, depth of discharge and sun hours.
How it works — Off-Grid Solar & Battery System Sizing
Inputs
- Eday
- Daily AC energy use (Wh)
- DoD
- Depth of discharge (%)
- C, V
- Battery bank voltage
- PSH
- Peak sun hours (worst month) (h)
Formula
- E_b = E_ac/η_inv·days/DoD
- C = E_b/V
- P_pv = E_dc/(η_b·PSH·PR)
Results
- C
- Battery capacity
- Ppv
- PV array required
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
E_b = E_ac/η_inv·days/DoD · C = E_b/V · P_pv = E_dc/(η_b·PSH·PR)
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Constant daily load; the PV array is sized for the worst month's sun hours.
- Battery chemistry limits (temperature, ageing, C-rate) are not modelled beyond the depth of discharge you set.
References
- IEEE Std 1013: Sizing lead-acid batteries for stand-alone PV systems
- IEEE Std 1562: Array and battery sizing in stand-alone PV systems
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Solar PV String & Array Sizing Modules per string and parallel strings from temperature-corrected module voltages and the inverter's MPPT window, array power, I–V curve and an annual energy estimate. Open tool
- Electrical Engineering Battery Pack Builder (Series/Parallel, C-Rate, Runtime) Pack voltage, capacity, energy, current and power limits of a series–parallel battery pack from cell data, with the C-rate and runtime at a load. Open tool
- Electrical Engineering Battery Runtime How long a battery bank can power a load, allowing for depth of discharge and inverter efficiency. Open tool
- Electrical Engineering Wind Turbine Power & Annual Energy Power in the wind, extracted power with C_p, power curve, Rayleigh wind distribution, annual energy, capacity factor and sensitivity to the mean wind speed; air density from the shared standard atmosphere. Open tool