Level 1 — Basic calculation

Interactive Phasor Diagram & Power Triangle

Drag the current phasor or the phase-angle slider and see real, reactive and apparent power and the power factor update, for single-phase and balanced wye or delta loads.

How it works — Interactive Phasor Diagram & Power Triangle

V I φ P = S·cosφ Q = S·sinφ

Inputs

V
Voltage (line-to-line for three-phase) (V)
I
Line current (A)
φ
Phase angle φ (current lagging +) (°)

Formula

  • S = V·I (single) · S = 3·V_ph·I_ph
  • P = S·cosφ
  • Q = S·sinφ
  • wye: V_ph = V_L/√3 · delta: I_ph = I_L/√3

Results

P
Real power P
Q
Reactive power Q
S
Apparent power S
PF
Power factor

Interactive phasor diagram

Drag the tip of the current phasor around the circle, or use the slider: the phase angle, the powers and the power factor update.

P
Q
S
Power factor
Load

Positive: current lags the voltage (inductive load); negative: leads (capacitive).

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

S = V·I (single) · S = 3·V_ph·I_ph · P = S·cosφ · Q = S·sinφ · wye: V_ph = V_L/√3 · delta: I_ph = I_L/√3

Formulas are evaluated in SI units; inputs and results are converted.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 1 — Basic calculation

A direct engineering equation.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Sinusoidal supply; three-phase loads are balanced.
  • The voltage phasor is the reference (0°).

References

  • IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
  • J. W. Nilsson, S. A. Riedel, Electric Circuits

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.