Level 1 — Basic calculation
AC Power & Power Factor Correction
Real, reactive and apparent power with the power triangle, plus the capacitor bank that raises the power factor to a target.
How it works — AC Power & Power Factor Correction
Inputs
- V
- Voltage (line-to-line for three-phase) (V)
- I
- Line current (A)
- cos φ
- Present power factor (lagging)
- cos φ2
- Target power factor
Formula
- S = √3·V·I
- P = S·cosφ
- Q_c = P(tanφ₁ − tanφ₂)
Results
- P
- Real power
- Q
- Reactive power
- S
- Apparent power
- Qc
- Capacitor bank for target power factor
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
S = V·I (·√3) · P = S·cosφ · Q = P·tanφ · Q_c = P(tanφ₁ − tanφ₂)
Formulas are evaluated in SI units; inputs and results are converted.
Size the bank a little below the calculated value when loads vary, to avoid a leading power factor at light load.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 1 — Basic calculation
A direct engineering equation.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Sinusoidal supply; three-phase loads are balanced.
- Lagging (inductive) load; harmonics are ignored.
- Three-phase banks are delta-connected, so each capacitor sees the line-to-line voltage.
References
- IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
- IEEE Std 18: Shunt power capacitors
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Ohm's Law & Power Current, power and conductance from voltage and resistance. Open tool
- Electrical Engineering Three-Phase Power Real, apparent and reactive power of a balanced three-phase load. Open tool
- Electrical Engineering Series & Parallel Resistors Equivalent resistance of resistors connected in series or in parallel. Open tool
- Electrical Engineering DC Circuit Solver (Kirchhoff's Laws, Nodal Analysis) Solve any linear DC network of resistors and voltage and current sources: node voltages, branch currents, powers and the KCL/KVL check, by modified nodal analysis. Open tool