Level 1 — Basic calculation

AC Power & Power Factor Correction

Real, reactive and apparent power with the power triangle, plus the capacitor bank that raises the power factor to a target.

How it works — AC Power & Power Factor Correction

P Q S Qc φ

Inputs

V
Voltage (line-to-line for three-phase) (V)
I
Line current (A)
cos φ
Present power factor (lagging)
cos φ2
Target power factor

Formula

  • S = √3·V·I
  • P = S·cosφ
  • Q_c = P(tanφ₁ − tanφ₂)

Results

P
Real power
Q
Reactive power
S
Apparent power
Qc
Capacitor bank for target power factor
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

S = V·I (·√3) · P = S·cosφ · Q = P·tanφ · Q_c = P(tanφ₁ − tanφ₂)

Formulas are evaluated in SI units; inputs and results are converted.

Size the bank a little below the calculated value when loads vary, to avoid a leading power factor at light load.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 1 — Basic calculation

A direct engineering equation.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Sinusoidal supply; three-phase loads are balanced.
  • Lagging (inductive) load; harmonics are ignored.
  • Three-phase banks are delta-connected, so each capacitor sees the line-to-line voltage.

References

  • IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
  • IEEE Std 18: Shunt power capacitors

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.