Level 2 — Engineering approximation

Solar PV String & Array Sizing

Modules per string and parallel strings from temperature-corrected module voltages and the inverter's MPPT window, array power, I–V curve and an annual energy estimate.

How it works — Solar PV String & Array Sizing

Ns ~ Voc(T) MPPT

Inputs

Voc
Open-circuit voltage V_oc (V)
β
Voltage temperature coefficient β (%/°C)
Tmin
Minimum ambient temperature (°C)
MPPT
MPPT maximum voltage (V)

Formula

  • V_oc,cold = V_oc(1 + β(T_min − 25))
  • N_max = ⌊V_max/V_oc,cold⌋
  • N_min = ⌈V_MPPT,min/V_mp,hot⌉
  • N_p ≤ I_max/(1.25I_sc)

Results

Ns
Modules per string (used)
P
Array DC power
Module (STC datasheet)
Site
Inverter
Array
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

V_oc,cold = V_oc(1 + β(T_min − 25)) · N_max = ⌊V_max/V_oc,cold⌋ · N_min = ⌈V_MPPT,min/V_mp,hot⌉ · N_p ≤ I_max/(1.25I_sc)

Formulas are evaluated in SI units; inputs and results are converted.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 2 — Engineering approximation

A preliminary engineering model with the simplifications listed under Assumptions.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • The V_oc temperature coefficient is also applied to V_mp (use the V_mp coefficient if the datasheet gives one).
  • 1.25·I_sc per string for the current limit; irradiance enhancement above 1000 W/m² is not modelled.
  • Energy = DC power × peak sun hours × performance ratio × 365 (a first estimate, not a simulation).

References

  • IEC 62548: Photovoltaic arrays — design requirements
  • NEC Article 690: Solar photovoltaic systems
  • W. Xiao, W. G. Dunford, A. Capel (2004), A novel modeling method for photovoltaic cells, IEEE PESC

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.