Level 2 — Engineering approximation

Synchronous Generator: EMF, Load Angle & Regulation

Speed from frequency and poles, rated current, internal EMF, load angle, voltage regulation, shaft power and torque of a cylindrical-rotor synchronous generator.

How it works — Synchronous Generator: EMF, Load Angle & Regulation

G Vφ EA jX·I δ

Inputs

S
Load (apparent power) (kVA)
Vφ
Line-to-line voltage (V)
Xs
Synchronous reactance X_s (per phase) (Ω)
p
Number of poles

Formula

  • n_s = 120f/p
  • E_A = V_φ + (R_A + jX_s)·I_A
  • VR = (E_A − V_φ)/V_φ
  • P_max = 3E_AV_φ/X_s

Results

EA
Internal EMF (line-to-line)
δ
Load (power) angle δ
ns
Synchronous speed
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

n_s = 120f/p · E_A = V_φ + (R_A + jX_s)·I_A · VR = (E_A − V_φ)/V_φ · P_max = 3E_AV_φ/X_s

Formulas are evaluated in SI units; inputs and results are converted.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 2 — Engineering approximation

A preliminary engineering model with the simplifications listed under Assumptions.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Cylindrical (round) rotor; constant synchronous reactance (no saturation).
  • Wye-connected armature.
  • Sinusoidal supply; three-phase loads are balanced.

References

  • S. J. Chapman, Electric Machinery Fundamentals
  • IEEE Std 115: Test procedures for synchronous machines

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.