Pipe Insulation Heat Loss

Heat loss from an insulated pipe, the insulation surface temperature and the saving against a bare pipe.

How it works — Pipe Insulation Heat Loss

Tf r1 r2 q′ T∞ h

Inputs

r1
Pipe outside diameter (in)
r2 − r1
Insulation thickness (in)
k
Insulation conductivity k (BTU/h·ft·°F)
h
Outside film coefficient h (BTU/h·ft²·°F)
Tf
Fluid temperature (°F)
T∞
Ambient temperature (°F)

Formula

  • q′ = ΔT / [ln(r₂/r₁)/2πk + 1/2πr₂h]
  • r_c = k / h

Results

q′
Heat loss per length
Ts
Insulation surface temperature
rc
Critical insulation radius

Mineral wool ≈ 0.04, calcium silicate ≈ 0.06, elastomeric foam ≈ 0.035

Still indoor air incl. radiation ≈ 8–12, outdoors ≈ 20–30

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

q′ = ΔT / [ln(r₂/r₁)/2πk + 1/(2πr₂h)] · r_c = k/h

Formulas are evaluated in SI units; inputs and results are converted.

Surface temperatures above 60 °C are flagged as a burn risk. If the critical radius exceeds the pipe radius, thin insulation can increase heat loss.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Assumptions

  • Steady state, radial conduction only.
  • Thermal conductivity constant with temperature.
  • Pipe wall and inside film resistances are neglected (conservative: slightly overstates the loss).
  • Radiation is not modelled separately; include it in the film coefficient if significant.

References

  • F. P. Incropera et al., Fundamentals of Heat and Mass Transfer
  • ASTM C680: Heat gain or loss and surface temperatures of insulated pipe
  • ASTM C1055: Heated system surface conditions that produce contact burn injuries

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.