Psychrometric Calculator

Moist-air properties from dry bulb plus RH, wet bulb or dew point, with mixing, heating and cooling processes plotted on a psychrometric chart.

How it works — Psychrometric Calculator

T W φ = 100 % φ h

Inputs

T
Dry-bulb temperature (°C)
φ
Value of the second property
z
Altitude (m)

Formula

  • W = 0.622·p_w/(p − p_w)
  • h = 1.006T + W(2501 + 1.86T)

Results

W
Humidity ratio
h
Enthalpy
Tdp
Dew point
Twb
Wet-bulb temperature
Air state 1

% for relative humidity; °C (or °F in imperial) for wet bulb and dew point

Mix with a second stream (optional)
Heating or cooling coil (optional)
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

W = 0.621945·p_w/(p − p_w) · h = 1.006T + W(2501 + 1.86T) · v = 0.287042(T + 273.15)(1 + 1.6078W)/p

Imperial enthalpy is referenced to dry air at 0 °F, as on ASHRAE IP charts.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Assumptions

  • Moist air as an ideal-gas mixture (ASHRAE formulation).
  • An ideal cooling coil: below the dew point the air leaves saturated at the supply temperature.
  • Mixing is adiabatic and by dry-air mass fraction.

References

  • ASHRAE Handbook — Fundamentals
  • R. W. Hyland, A. Wexler (1983), ASHRAE Transactions 89(2A)

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.