Psychrometric Calculator
Moist-air properties from dry bulb plus RH, wet bulb or dew point, with mixing, heating and cooling processes plotted on a psychrometric chart.
How it works — Psychrometric Calculator
Inputs
- T
- Dry-bulb temperature (°F)
- φ
- Value of the second property
- z
- Altitude (ft)
Formula
- W = 0.622·p_w/(p − p_w)
- h = 1.006T + W(2501 + 1.86T)
Results
- W
- Humidity ratio
- h
- Enthalpy
- Tdp
- Dew point
- Twb
- Wet-bulb temperature
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
W = 0.621945·p_w/(p − p_w) · h = 1.006T + W(2501 + 1.86T) · v = 0.287042(T + 273.15)(1 + 1.6078W)/p
Formulas are evaluated in SI units; inputs and results are converted.
Imperial enthalpy is referenced to dry air at 0 °F, as on ASHRAE IP charts.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Assumptions
- Moist air as an ideal-gas mixture (ASHRAE formulation).
- An ideal cooling coil: below the dew point the air leaves saturated at the supply temperature.
- Mixing is adiabatic and by dry-air mass fraction.
References
- ASHRAE Handbook — Fundamentals
- R. W. Hyland, A. Wexler (1983), ASHRAE Transactions 89(2A)
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Mechanical tools
- Mechanical Gear Ratio & Output Speed Ratio, output speed, torque and power of a simple gear pair. Open tool
- Mechanical Bolt Tightening Torque Preload and tightening torque for ISO metric and UNC inch bolts by grade and nut factor. Open tool
- Mechanical Pipe Pressure Drop (Darcy–Weisbach) Friction pressure loss, velocity and Reynolds number for flow in a straight circular pipe. Open tool
- Mechanical Pump Head, Power & NPSH Total dynamic head, shaft and motor power, NPSH available and the system curve for a pumping line. Open tool