Level 2 — Engineering approximation
Standby Generator Sizing (Running Load & Motor Starting)
Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance.
How it works — Standby Generator Sizing (Running Load & Motor Starting)
Inputs
- Sstart
- Largest motor (started last) (kW)
- Xd″
- Generator subtransient reactance X″d (%)
- ΔV
- Allowed voltage dip (%)
Formula
- S_run = P/PF
- S_start = P_m·(LRkVA/kW)·k
- ΔV ≈ X″d/(X″d + S_gen/S_start)
- P_gen = S_gen·PF_gen
Results
- G
- Recommended standby generator rating
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
S_run = P/PF · S_start = P_m·(LRkVA/kW)·k · ΔV ≈ X″d/(X″d + S_gen/S_start) · P_gen = S_gen·PF_gen
Formulas are evaluated in SI units; inputs and results are converted.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- The largest motor starts last with all other loads running; one load step.
- Voltage dip from the subtransient reactance only (AVR response ignored).
References
- IEEE Std 446 (Orange Book): Emergency and standby power systems
- NEMA MG 1: Motors and generators
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Building Electrical Load & Transformer Size Connected and demand load, power factor, current, diversity and the next standard transformer size from a load schedule with your own demand factors. Open tool
- Electrical Engineering Induction Motor Equivalent Circuit & Torque–Speed Curve Synchronous speed, slip, stator current, power flow, efficiency, starting and pull-out torque of a three-phase induction motor from its per-phase equivalent circuit. Open tool
- Electrical Engineering Synchronous Generator: EMF, Load Angle & Regulation Speed from frequency and poles, rated current, internal EMF, load angle, voltage regulation, shaft power and torque of a cylindrical-rotor synchronous generator. Open tool
- Electrical Engineering Cable Voltage Drop Resistive voltage drop and power loss in single-phase and three-phase cable runs. Open tool