Level 2 — Engineering approximation
Induction Motor Equivalent Circuit & Torque–Speed Curve
Synchronous speed, slip, stator current, power flow, efficiency, starting and pull-out torque of a three-phase induction motor from its per-phase equivalent circuit.
How it works — Induction Motor Equivalent Circuit & Torque–Speed Curve
Inputs
- V
- Line-to-line voltage (V)
- f
- Frequency (Hz)
- p
- Number of poles
- s
- Slip (%)
- R2
- Rotor resistance R₂ (referred) (Ω)
Formula
- n_s = 120f/p
- s = (n_s − n_m)/n_s
- P_AG = 3I₂²R₂/s
- τ = P_AG/ω_s
- P_conv = (1 − s)P_AG
Results
- ns
- Synchronous speed
- nm
- Rotor speed
- T
- Induced torque
- η
- Efficiency
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
n_s = 120f/p · s = (n_s − n_m)/n_s · P_AG = 3I₂²R₂/s · τ = P_AG/ω_s · P_conv = (1 − s)P_AG
Formulas are evaluated in SI units; inputs and results are converted.
The default values reproduce Chapman's worked example of a 460 V, 25 hp, four-pole motor at 2.2 % slip.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 2 — Engineering approximation
A preliminary engineering model with the simplifications listed under Assumptions.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Wye-connected stator; per-phase T equivalent circuit with constant parameters (no saturation or deep-bar effect).
- Core losses are lumped with the rotational losses.
- Sinusoidal supply; three-phase loads are balanced.
References
- S. J. Chapman, Electric Machinery Fundamentals
- IEEE Std 112: Test procedure for polyphase induction motors and generators
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Motor Sizing & Full-Load Current Standard motor rating for a load, with synchronous and rated speed, torque, full-load and starting current. Open tool
- Electrical Engineering Standby Generator Sizing (Running Load & Motor Starting) Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance. Open tool
- Electrical Engineering Cable Sizing (Ampacity, Voltage Drop, Fault) Smallest copper conductor for a circuit after temperature and grouping derating, breaker coordination, voltage drop and short-circuit withstand. Open tool
- Electrical Engineering DC Motor Speed, Torque & PWM Drive Steady-state speed, current, back-EMF, power and efficiency of a permanent-magnet or separately excited DC motor driven by a PWM duty cycle. Open tool