Level 2 — Engineering approximation

Motor Sizing & Full-Load Current

Standard motor rating for a load, with synchronous and rated speed, torque, full-load and starting current.

How it works — Motor Sizing & Full-Load Current

T n I

Inputs

P
Load shaft power (kW)
V
Line voltage (three-phase) (V)
p
Poles
η
Full-load efficiency (%)

Formula

  • n_s = 120f/p
  • T = P/ω
  • I = P/(√3·V·η·cosφ)

Results

n
Full-load speed
T
Rated torque
I
Full-load current

IE3 11–15 kW ≈ 91–92 %

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

n_s = 120f/p · T = P/ω · I = P/(√3·V·η·cosφ)

Use the nameplate or catalogue current for protection settings; this estimate uses the efficiency and power factor you enter.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 2 — Engineering approximation

A preliminary engineering model with the simplifications listed under Assumptions.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Three-phase induction motor at rated voltage and frequency.
  • Starting current multipliers are typical values; check the motor's locked-rotor code.
  • Sinusoidal supply; three-phase loads are balanced.

References

  • IEC 60034-1 / IEC 60034-30-1 (ratings, IE efficiency classes)
  • NEMA MG 1: Motors and Generators
  • IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.