Level 2 — Engineering approximation

Transformer Currents, Fault Level & Regulation

Primary and secondary full-load currents, turns ratio, secondary short-circuit current and voltage regulation of a transformer.

How it works — Transformer Currents, Fault Level & Regulation

V1 V2 Z%

Inputs

V1
Primary voltage (V)
V2
Secondary voltage (V)
Z%
Impedance Z (%)

Formula

  • I = S/(√3·V)
  • I_sc = I₂ / Z

Results

I2
Secondary full-load current
Isc
Secondary fault current (infinite source)
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

I = S/(√3·V) · I_sc = I_FL / Z · VR ≈ R cosφ + X sinφ

Formulas are evaluated in SI units; inputs and results are converted.

The fault current assumes an infinite upstream source, so it is an upper bound for the transformer's own contribution.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 2 — Engineering approximation

A preliminary engineering model with the simplifications listed under Assumptions.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Sinusoidal supply; three-phase loads are balanced.
  • Infinite-bus primary; no motor contribution to the fault.

References

  • IEC 60076-1 / IEEE C57.12.00: Power transformers
  • IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.