Level 1 — Basic calculation

Cable Voltage Drop

Resistive voltage drop and power loss in single-phase and three-phase cable runs.

How it works — Cable Voltage Drop

Z I L A · ρ Vs ΔV

Inputs

Vs
Supply voltage (V)
I
Load current (A)
L
One-way length (ft)
A
Conductor size
ρ
Conductor
~
System

Formula

  • ΔV₁φ = 2·I·ρL/A
  • ΔV₃φ = √3·I·ρL/A

Results

ΔV
Voltage drop
Vload
Voltage at load
Ploss
Cable power loss
Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

ΔV₁φ = 2·I·ρL/A · ΔV₃φ = √3·I·ρL/A

Formulas are evaluated in SI units; inputs and results are converted.

Resistance at 20 °C; reactance and conductor temperature rise are ignored, which is conservative only for small cables.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Calculation level & design standard

Level 1 — Basic calculation

A direct engineering equation.

Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.

Assumptions

  • Conductor resistance at 20 °C; reactance is ignored.
  • Balanced three-phase load; single-phase drop counts both conductors.
  • Allowed drop is often 3 % for branch circuits and 5 % overall; check your code.

References

  • IEC 60364-5-52 / CEC Part I / NEC Chapter 9 — conductor data
  • IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.