Level 1 — Basic calculation
Cable Voltage Drop
Resistive voltage drop and power loss in single-phase and three-phase cable runs.
How it works — Cable Voltage Drop
Inputs
- Vs
- Supply voltage (V)
- I
- Load current (A)
- L
- One-way length (m)
- A
- Conductor size (mm²)
- ρ
- Conductor
- ~
- System
Formula
- ΔV₁φ = 2·I·ρL/A
- ΔV₃φ = √3·I·ρL/A
Results
- ΔV
- Voltage drop
- Vload
- Voltage at load
- Ploss
- Cable power loss
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
ΔV₁φ = 2·I·ρL/A · ΔV₃φ = √3·I·ρL/A
Resistance at 20 °C; reactance and conductor temperature rise are ignored, which is conservative only for small cables.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Calculation level & design standard
Level 1 — Basic calculation
A direct engineering equation.
Preliminary engineering calculation — no jurisdiction-specific code compliance claimed. Verify the applicable requirements with a qualified professional.
Assumptions
- Conductor resistance at 20 °C; reactance is ignored.
- Balanced three-phase load; single-phase drop counts both conductors.
- Allowed drop is often 3 % for branch circuits and 5 % overall; check your code.
References
- IEC 60364-5-52 / CEC Part I / NEC Chapter 9 — conductor data
- IEEE Std 141 (Red Book): Electric Power Distribution for Industrial Plants
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Electrical Engineering tools
- Electrical Engineering Cable Sizing (Ampacity, Voltage Drop, Fault) Smallest copper conductor for a circuit after temperature and grouping derating, breaker coordination, voltage drop and short-circuit withstand. Open tool
- Electrical Engineering Building Electrical Load & Transformer Size Connected and demand load, power factor, current, diversity and the next standard transformer size from a load schedule with your own demand factors. Open tool
- Electrical Engineering Panel Schedule & Phase Balance Phase loads, imbalance, phase currents and demand of a three-phase panelboard from a list of circuits, with a phase-balance chart. Open tool
- Electrical Engineering Standby Generator Sizing (Running Load & Motor Starting) Preliminary standby generator rating from the running load and the largest motor started last, checking the transient voltage dip with the generator's subtransient reactance. Open tool