Heat Exchanger (ε-NTU & LMTD)

Duty and outlet temperatures of counterflow, parallel-flow and shell-and-tube exchangers from U and area, with an LMTD check and temperature profile.

How it works — Heat Exchanger (ε-NTU & LMTD)

Th,in Th,out Tc,in Tc,out UA

Inputs

Th,in
Hot inlet temperature (°F)
Tc,in
Cold inlet temperature (°F)
U
Overall coefficient U (clean) (BTU/h·ft²·°F)
A
Heat transfer area (ft²)

Formula

  • NTU = UA/C_min
  • Q = ε·C_min·ΔT_max
  • Q = UA·F·ΔT_lm

Results

Q
Heat duty
Th,out
Hot outlet temperature
Tc,out
Cold outlet temperature
ε
Effectiveness ε
Hot stream

Water ≈ 4180, light oil ≈ 2000, air ≈ 1005

Cold stream
Exchanger

Water–water plate ≈ 3000–6000, shell and tube ≈ 800–1500, gas–liquid ≈ 20–300

Reset

Results

Enter your values and press Calculate. The defaults are a worked example.

Formula

NTU = UA/C_min · Q = ε·C_min·(T_h,in − T_c,in) · Q = U·A·F·ΔT_lm

Formulas are evaluated in SI units; inputs and results are converted.

An LMTD correction factor F below 0.75 is flagged: add shells in series or change the arrangement.

Show the math

Worked solution

Press Calculate to see every step with your values substituted.

Assumptions

  • Steady state; constant specific heats and U over the exchanger.
  • No heat loss to the surroundings and no phase change.
  • Fouling adds in series: 1/U_f = 1/U + R_f.

References

  • F. P. Incropera et al., Fundamentals of Heat and Mass Transfer
  • TEMA Standards, 10th ed.
  • R. K. Shah, D. P. Sekulić, Fundamentals of Heat Exchanger Design

Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.