Heat Exchanger (ε-NTU & LMTD)
Duty and outlet temperatures of counterflow, parallel-flow and shell-and-tube exchangers from U and area, with an LMTD check and temperature profile.
How it works — Heat Exchanger (ε-NTU & LMTD)
Inputs
- Th,in
- Hot inlet temperature (°C)
- Tc,in
- Cold inlet temperature (°C)
- U
- Overall coefficient U (clean) (W/m²·K)
- A
- Heat transfer area (m²)
Formula
- NTU = UA/C_min
- Q = ε·C_min·ΔT_max
- Q = UA·F·ΔT_lm
Results
- Q
- Heat duty
- Th,out
- Hot outlet temperature
- Tc,out
- Cold outlet temperature
- ε
- Effectiveness ε
Inputs
Results
Enter your values and press Calculate. The defaults are a worked example.
Formula
NTU = UA/C_min · Q = ε·C_min·(T_h,in − T_c,in) · Q = U·A·F·ΔT_lm
An LMTD correction factor F below 0.75 is flagged: add shells in series or change the arrangement.
Show the math
Worked solution
Press Calculate to see every step with your values substituted.
Assumptions
- Steady state; constant specific heats and U over the exchanger.
- No heat loss to the surroundings and no phase change.
- Fouling adds in series: 1/U_f = 1/U + R_f.
References
- F. P. Incropera et al., Fundamentals of Heat and Mass Transfer
- TEMA Standards, 10th ed.
- R. K. Shah, D. P. Sekulić, Fundamentals of Heat Exchanger Design
Results are for preliminary design and education. Verify against the governing code and have critical work checked by a licensed professional engineer.
More Mechanical tools
- Mechanical Gear Ratio & Output Speed Ratio, output speed, torque and power of a simple gear pair. Open tool
- Mechanical Bolt Tightening Torque Preload and tightening torque for ISO metric and UNC inch bolts by grade and nut factor. Open tool
- Mechanical Pipe Pressure Drop (Darcy–Weisbach) Friction pressure loss, velocity and Reynolds number for flow in a straight circular pipe. Open tool
- Mechanical Pump Head, Power & NPSH Total dynamic head, shaft and motor power, NPSH available and the system curve for a pumping line. Open tool